[Optional Accessory] When inputting AC100V to the isolation transformer TF-2302P and checking the output side L1-PE and L2-PE with a tester, the readings vary between 70V and 30V each time. Is this normal?

[Optional Accessory] When inputting AC100V to the isolation transformer TF-2302P and checking the output side L1-PE and L2-PE with a tester, the readings vary between 70V and 30V each time. Is this normal?

This is normal. When measuring the secondary side of the isolation transformer without connecting anything, there is no reference because it is floating from ground.
Please verify that 100V is measured between L1-L2.